"TYPICAL"
HAZ-SAFE BUILDINGS, INC. SPECIFICATION FOR:
1.0
GENERAL BUILDING, CONSTRUCTION, AND PERFORMANCE:
1.1
One (1) factory built, self-contained, relocatable, modular Haz-Safe
Building, wide x long x high (including 4" high roof top crane
lifting lugs), with overall building footprint of ft.5. The interior shall be one whole room, wide x long
x high, with a total of ft.5 of usable floor space. Interior dimensions shall have
priority over exterior dimensions. Placement of the module(s) by user=s crane at site and user facility=s hand wiring of the electrical power supply system
to the building=s prewired entrance panel(s), interconnection of user
supplied operation mechanicals (cabling, plumbing, etc.) at building=s prepared penetrations shall complete field installation. (The interior
ceiling height is less than or exceeds the OSHA regulation
per 29CFR 1910.37(I), Headroom "...shall be so designed and maintained
as to provide adequate headroom, but in NO case shall the ceiling be
less than 7 feet 6 inches...." Also see Structural Loads, paragraph
1.2.2 and Interior Lighting, paragraph 3.2.1.)
Storage Capacity shall be for up to:
( ) fifty-five (55) gallon drums or ( )
4' square pallets stored back-to-front and side-to-side completely filling
all available floor space. Total room storage capacity is ( )
gallons in "packed-in" mode.
- OR -
( ) fifty-five (55) gallon drums or ( )
4' square pallets stored with ( ") wide aisle for inspection
and material handling of hand trucks, lifters, forklifts and crane hoists
maneuvering capability. Total room storage capacity is ( ) gallons
less floor space allowed for aisles.
1.2
PROTECTED CRADLE AND CROWN CONSTRUCTION: (True
heavy gauge steel construction has to do with the quantity and quality
(see paragraph 1.4) of the steel used. For example, 1/4" thick
steel has, by weight, 186% more steel than 10 gauge which has 281% more
steel than 18 gauge! An all-steel building is classified as non-combustible
and is acceptable, in most applications, for enclosures of corrosive
or toxic chemicals without making the building fire rated. When located
more than 75' away from other facilities, roads or property lines, fire
rating is not necessary for flammable and combustible chemicals. Should
the building require heating or cooling systems, then the walls and
ceiling/roof would have to be insulated. The exposed insulation material
should be covered for mechanical protection. This can be efficiently
achieved with gypsum wall board which incidentally will fire rate the
building.)
1.2.1 Heavy Duty Building shall have a continuously welded steel
skeleton of 1/4" thick wall tubular (square or rectangular) members
starting at the cradle (base) with 4" wide x 6" high tubes
all around the perimeter. The lifting crown shall have 4" x 4"
tubes all around the top of the building. Vertical wall members shall
be 2" x 4" tubes in all corners, and on 24" centers shall
be 2" x 2" tubes filling in the front, back, and end walls.
(Thin common steel, up to 10 gauge thick, for studs, joists or purlins
shall not be acceptable as wall or roof members.) There shall be 2"
x 4" tubes (non combustible buildings only) or 2-1/2" x 4"
or 6" high recessed structural steel channel inside the lifting
crown framework (fire rated or insulated buildings) on 24" centers
spanning the width of the roof. The exterior skin of the building shall
be 10 gauge temper pass carbon plate steel applied in 48" wide
sheets on the walls and roof, spot welded in place every 12" from
the inside of the building and seam welded (continuous) at plate junctures
and structure periphery on the outside for a "sealed up" rugged
structure. Building shall be ideally suited for heavy duty industrial
usage to resist damage during lifting operations or vehicular impact
resistance such as forklift impact and punctures as may occur from the
forklift forks and from forklift loads with protrusions and Asprigitly sprockets@ attached to
industrial equipment that could ding or even penetrate a light, thinly
constructed building. (Lightweight or thin steel skins, plywood, or
rubber membranes shall not be used, and no mechanical fasteners, vertical
battens, such as exposed screws, fasteners, or rivets, shall be used
to attach or penetrate the exterior skin. See Paragraph 5.5.1, Warranty.)
1.2.2 Structural Loads as described by Factory Mutual (FM) approval
standard for Flammable and Combustible Liquid Storage Buildings, Class
Number 6049, as defined by N.F.P.A. 30 shall be:
X
100 lbs. ft.5 (488 kg/m5) internal blast resistance. (The basic construction
in paragraph 1.2.1 has a 120 lbs. ft.5 blast rating. Higher ratings shall be easily
achieved by either reducing space between vertical members and/or increasing
tubular members wall thickness or size and/or adding the resistance
values of insulation and wall board applied on the interior [see note
at bottom of paragraph 2.3.1]. This is important when using upgraded
stiffer N.F.P.A. 68 standard, paragraph 5.3 equations for enclosure
strength and relief venting. Equivalent Factory Mutual Property Loss
Prevention Data Sheet 1-44, Damage Limiting Construction, paragraph
1.0 Scope states, "Recommended combinations of vent area and design
pressures for pressure-resistant construction are addressed for
gas/air deflagrations. The criteria varies depending on the degree of
hazard of the fuel(s) involved.")
X
90 mph (144 km/h) wind load, to a velocity pressure of 21 lbs.
ft.5
X
40 lbs. ft.5 (195 kg/m5) roof snow load, plus the weight of the roof construction
and any roof installed components.
X
250 lbs. ft.5 (1220 kg/m5) floor support system under dry conditions.
X
Zone 4 Seismic Condition.
NOTE: Haz-Safe blast resistance calculations are based
on only the structural strength of the tubular frame and exterior steel
plate as described in paragraph 1.2.1. This means, when adding on one
or both sides of the tubular frame, steel furring strips, layer(s) of
gypsum and the porcelain enamel steel finish (as described in paragraph
2.3.1, 2.3.2, and 2.3.3), the blast capabilities are considerably increased.
Most other steel buildings use the resistance of all parts of the wall
and roof construction to barely meet the 100 lbs. per sq. ft. requirements.
Also, other building manufacturers' published literature do not show
floor to ceiling heights above 7'4" and therefore do not have Factory
Mutual approval above 7'4"! In order to meet the above blast ratings,
walls higher than 7'4" need to be redesigned and resubmitted to
Factory Mutual. In general, to raise the wall, every 6" increase
in height would require approximately up to 20% more steel by weight
the entire length of each vertical wall member not just for the incremental
increase. Keep in mind FM approval is limited to published heights.
Haz-Safe buildings are pre-approved to 16' high!
1.2.3 Optional Modular Building System shall
be applied to the building(s) with manufacturing done in two (2) modular
end units, each or one ( ) wide x ( ) long and the other ( ) wide x
( ) long, bolted together at the factory and shipped to client's location
(or shipped separately and bolted together at client's location for
large multi-module building). There shall be a large 1/2" thick
tubular rafter ( " high x " wide) at the crown of the
open wall of each end unit to meet all load specifications as described
in paragraph 1.2.2 and to provide a clear span the length of the building
(up to 30'. Buildings [longer than 30'] shall have a single floor-to-ceiling
column or post in the middle of the building). The patented roof and
floor joints between modules shall be covered with a 12 gauge steel
cap. (The floor cap prevents spills from getting into the environment.)
The floor cap shall be secured (a) by having a "hat" with
a brim shape, (b) with the brim of the "hat" being bolted
to steel angles that are welded to the inside wall of the two sumps,
and (c) with the elevated flooring (see paragraph 1.7) sitting down
on the top of the brim. The flooring shall be flush with the top of
the modular joint cap. The roof cap shall extend above the roof seven
(7) inches covering the crane lifting lugs which become flanges for
bolting the roof together. The finished building shall have the appearance
of a non-modular whole building.
Expansion Mid Units shall be available to be
delivered complete so that at any time in the future, the initial building
can be unbolted and split to accept a new mid module. Mid modules shall
be available in any width increment (up to 14' wide interior) to increase
the storage capacity of the above building. The engineered drawings
shall be designed assuming the above modules shall be separated in the
future in order to accept a mid module of the same size so that the
future building shall be 33% larger or up to 1500 square feet.
During the initial installation or installation of a
future mid unit, the modules are separated and brought together by crane,
aligning two (2), three (3), etc. 4" square aligning tubes welded
under each module's floor. Each of these tubes shall become a sealed
enclosure to house a 1" diameter threaded rod. There shall be a
two directional (side to side or up and down) aligning sleeve partially
inserted into the tubes at the joint between each modular unit as they
are being brought together by onsite crane to approximately 6"
of each other. The 1" rods are fed into the aligning tubes of the
first module past the sleeve at the mid joint and through the tubes
of the second module. The sleeve shall be designed to maintain all loads
as described in paragraph 1.2.2, and shall maintain loads and joint
connection in a Zone 4 earthquake environment. 1" dia. nuts on
1/2" thick x 4" x 4" caps at each end of the tubes are
used to crank the modules together the last inch or two. Each rod and
tube combination shall have a minimum 17,000 lbs. compression capability.
The exterior wall joint shall be weather caulked and the interior ceiling
and wall joints shall be covered with porcelain enameled steel-finished
fire rated gypsum as described in paragraph 2.3. (Modular pre-fab hazmat
buildings as described here are protected by U.S. Patent Numbers 5,191,742,
5,285,617, and 5,396,742.)
1.3 Vendor Qualifications:
Only manufacturers regularly engaged in the design and construction
of Factory Mutual (FM) approved hazmat buildings and conforming to the
following trade and industrial standards and codes shall be considered.
Building shall exceed requirements of EPA, OSHA (29 CFR1910.106), RCRA
(40 CFR 264.1101), NFPA (17, 68, 70, and 91), UBC, UFC, BOCA National
Building Code/1993 and Subtitle 4, SBFP, NEMA, NEC, and NESC, as well
as ASTM, AISI, and AWS - and is approved by Factory Mutual with UL listed
components and fire wall construction.
For use of local building and fire authorities approving
process, manufacturer shall submit: (1) a copy of Factory Mutual approval
(upon request), (2) three sets of custom engineered drawings (average
[15] 'D' sized pages and available on one CD), and (3) optional
drawings stamped by a registered ( ) ( ) structural engineer
as a part of submittals.
User has responsibility of communicating with the authority
having jurisdiction and/or the insurance underwriter for concurrence
with the approach and design of building and all accessories and components.
1.4 All Metal Materials
- N.C. (Non-Combustible) Unitized Superstructure shall be ASTM-A Grade
500-B4 tubular steel stock and ASTM-A 36 channels - and (12 or 10) gauge
temper pass carbon plate steel shall be ASTM-A 567. All structural steel
members, doors, frames, and exposed metal components not having factory
prefinished coatings shall be painted with one (1) prime coat and two
(2) finish coats of Sherwin Williams industrial enamel HS coating (high
solids, low VOC, alkyd gloss top coat). Sump walls and floor shall be
painted with one (1) prime coat and two (2) coats of Sherwin Williams
industrial macropoxy HS high solids. All surfaces shall be prepared
per paint manufacturer's specification prior to application of prime
coat. Optional: All vertical wall and roof perimeter tubular
members shall be completely covered with continuously welded 10 gauge
temper pass carbon (ASTM 526G) steel plate with G-90 galvanized coating.
All structural members under the sump floor shall be hot dipped galvanized
after being cut to size. The exterior surface shall be painted with
two (2) coats of industrial and marine high solids macropoxy. (See Paragraph
5.5.2, Warranty.) Optional: Paint color selection and
accents shall be selected by user from paint manufacturer=s color chart,
and custom corporate color match and logos are available. Interior walls
and ceiling finishes are described in Paragraph 2.3.3.
1.5 A Minimum of Four
(4) Crane Lifting Lugs shall be strategically located and continuously
welded where vertical wall and roof members intersect the 4" x
4" tube at the roof edge along the long walls of the building.
Each lug shall have a minimum lifting capacity of 16,000 lbs., eliminating
rigging with full width spreader bars over the roof or slings under
the floor of the building. There shall be four (4) L-shaped tie-down
brackets at the base for wind and seismic bracing, and two (2)
forklifting 1/4" thick x 4" x 10" tubes under the
floor to permit lifting the building from the front and rear which prevents
forks from damaging or penetrating 10 gauge sump floor (user is required
to provide distance dimension between forklift tubes) - or - no forklifting
tubes under the floor of the building (modular buildings and buildings
over 10' wide and/or 18' long and/or 10' high should not be lifted with
a forklift).
1.5.1 Optional : A minimum of four (4) sunken/hidden-type
crane lifting lugs shall be recessed parallel with and down into
the above 4" x 4" tube (requires increasing width to 6").
Each lug shall have a pivoting clevis or shackle (up position for lifting
and down for storage within the tube). Outdoor buildings shall have
a neoprene gasket covered with a stainless steel plate bolted over the
clevis opening.
1.5.2 Optional Four (4) Universal-type Crane Lifting
Lugs shall be welded perpendicular onto the above 4" x 4"
tube where vertical wall and roof members intersect, and two (2) universal-type
lugs shall be welded perpendicular onto where vertical wall and under-the-floor
members intersect the 4" x 6" base tube on one (1) side of
the building. Universal-type lugs shall be capable of lifting both from
above the roof and the one side of the building to allow riggers to
lift and lay over the building on its other side for shipping purposes
and to reset building on its base at user's site.
1.6 Floor:
1.6.1 Sump shall be an integral spill containment
function located under an elevated floor and constructed of 1/4"
thick tubular steel, 6" high x 4" wide, surrounding its perimeter
and providing a 6" high double sump wall, and a 10 gauge steel
plate subfloor shall be laid on 4" high steel C-channels spaced
on 24" centers, all continuously welded together and hydrotested
before painting. Optional: Modular building and a multi-room
building shall require a sump in each module and in each room. Floor
is designed to be set on a flat concrete foundation provided by others.
(The installer of the foundation shall finish and measure the surface
so a gap at any point between concrete surface, as tested with an unleveled
freestanding 10' long straightedge, resting on any two high spots anywhere
on the surface, does not exceed 1/8". Verification to be provided
to CID prior to the shipment of Haz-Safe modules.) The sump shall have
( )% capacity of the total number of 55 gallon drums that could
be packed into building for a total of ( ) gallons (typical requirements
E.P.A. 10% and FM 25%). The 6" high sump plus 4" underneath
the building totals 10" of clearance over the door threshold. (The
rise or step spacing allowed by OSHA in 29 CFR 1010.24 "Fixed Industrial
Stairs" is between 6-1/2" and 9-1/2" high which means
a 10" high threshold is just slightly an unsafe height for a step
into or out of the building! Buildings with higher thresholds are even
more dangerous and are not acceptable.) Optional there shall
be a 4" high sump with ( )% at ( ) gallons which
shall have an ideal 8" high clearance over the top of the door
threshold. (This also helps shorten ramp lengths. See para. 4.8). The
four inch height under the sump floor shall allow for a 1-1/2"
diameter sump spill drain pipe (BOCA: 418.3.2.5) and for visual inspection
from outside underneath the floor. Optional under the floor heights
are available to increase drain pipe diameters. In addition to the above
sump capacity, the building shall have an option to contain 110%
plus a 20 or 30 minute discharge of the automatic water sprinkler system
(BOCA: 418.3.2.5). This shall require (a) the above 4" or 6"
sump height shall be increased to a total of ( ") high,
which shall provide a total of ( ) gallons capacity or (b) the
sump shall have one (two, etc.) ( ") diameter pipe penetration(s)
through the sump wall for a sprinkler water drain connection into a
separate reservoir or tank provided by the user. (The drainpipe(s) shall
be sized to prevent sprinkler water from overflowing the door thresholds.)
Optional sump wall shall be 1, 2, or 4 HRFR fire
rated with the gypsum covered with 10 gauge plate continuously welded
to the sump floor and the top of the perimeter sump tube.
1.6.2 Spark Resistant Elevated Flooring shall
be provided over the sump floor so when there is a spill, containers,
machinery, test equipment, etc. shall not be sitting-in, forklift's
wheels not passing through, and workers are not stepping in chemical
liquids. The elevated floor section (sized in removable sections) shall
be mechanically fastened to stainless steel floor supports to prevent
uneven joints to trip over. The grating shall be of dissimilar metal
than the floor supports so as to provide a spark resistant floor construction
(painted or galvanized carbon steel on top of stainless
steel floor supports). The support steel shall be continuously
welded to the sump wall and floor to prevent spilled chemicals from
getting under crevices, etc., and causing corrosion and hidden contamination.
(Elevated flooring and supports that are dropped, laid, or snapped into
place and plywood materials shall not be considered acceptable.) The
elevated floor shall be designed for 250 lb. ft.5 live load.
Elevated floor shall be 1" high with 1" wide
x 4" long openings painted, or optional galvanized
steel grating. Other options available:
X
1" high with 1/4" wide x 4" long openings galvanized
steel grating shall be installed in the aisle areas allowing a relatively
"smooth" surface for wheeled material handling vehicles to
maneuver. The aisle shall be over either the "V" connection
(para. 2.2.2) or the sloped trench (para 2.3.3) of the optional double
sloped floors. The fasteners holding the grating to the elevated supports
shall be counter sunk into the grating.
X
1/4" thick painted or galvanized, diamond or checker or smooth
steel plate in maximum 16 ft.5 sections shall be installed along the outside walls
and over the upper portions of the optional sloped sump floors for placement
of 55 gal. drums, pallets and tote tanks. Fasteners holding the plate
to the floor supports shall be countersunk into the plate. The plate
shall be installed so that there shall be a 1" gap between the
plate and the perimeter of the sump wall to allow a spilled chemical
to drain into the sump. The top surface of the smooth plate shall be
either gray epoxy painted or coated with a 100% solids 2 component epoxy
non-slip floor and deck coating. Coefficient of friction per ASTM F603
shall be Dry 1.0 and Wet 1.00. (Extending plate more than 4' toward
the interior option could cause extending the dry chem type fire suppression
system piping, sensors and discharge heads to be installed under the
plate.)
X
1" high fiberglass grating, T-beam fire rated protruded
type.
X
Any combination of the above.
1.6.3 Optional Floor Level Pallet Rack shall
be provided over the sump floor, constructed of painted 2" x 4"
tube steel laid flat that are continuously welded to the sump walls
at the door threshold height. The rack shall be designed for 250 lbs.
ft.5 live load.
1.6.4 Optional Second and Third Level Pallet Rack
shall be constructed of continuously welded 1/4" thick tubular
steel with the front edge of the horizontal rack being 1/4" thick
x 4" x 4" beam (forklift damage protection) and utilizing
2" x 4" tubes laid flat, providing a platform for the pallets.
The upper level rack shall have its own 6" deep sump which shall
be constructed as described in the above sump paragraph. There shall
be a minimum of 4" clearance from the top of a 40" high pallet
load sitting on the floor level rack to the bottom of the second level
rack and from the top of a 40" high pallet load sitting on the
second level rack to the bottom of the third level rack and from the
top of a 40" high pallet load sitting on the third level rack to
the top of the door opening. The racks shall be a minimum of 4' deep
with a 4" high angle backstop at the rear. The second and third
level racks shall be "free standing" with most of the load
bearing passed directly to the overhead door frames of the building.
The rack shall be designed for 250 lbs. ft.5 live load.
1.7 Interior Shall Be
Ergonomically Worker-Safe for handling hazardous material containers
near walls with all vents, conduits, ductwork, plumbing, fire suppression
and alarm system components, explosion relief panels, and heaters wall
mounted above 42" off the elevated floor, recessed into the wall,
or mounted in weatherproof housing on the exterior.
1.8 Water Runoff
shall be provided for all exterior (not in-plant) buildings with a minimum
of one (1) inch sloped roof and a drip edge over all standard doors
(not including overhead roll up) and explosion relief panels. The drip
edge shall be two (2) inches wide and angled down from wall of building.
2.0 HAZ-SAFE COMPONENTS:
2.1 Optional Sump Drain
(BOCA 418.3.2.5 Requirement) shall consist of a rectangular drain pit
of 1/4" thick steel with 4" high walls which are sunk down
from the sump floor plate to foundation level, and an optional
1" diameter polypropylene pipe mechanically fastened to the pit
wall. The pipe shall have a hand operated valve and a cap screwed on
the end. Optional: There shall be two drains per each room because
of the joint between modules creating more sumps.
2.2 Sloped Drainage
Systems - John LeBlanc, project engineer of Factory Mutual Research
Corporation's Standards Division, explains: "When we evaluate fire
protection for solids, our goal is to contain the fire to its point
of origin. We can't do that with liquids. When a liquid is pouring
across the floor, you can't stop the flow. The heat release rate of
a fire is controlled by the surface area available to burn. As the surface
area grows, so does the heat release rate...A well-arranged drainage
system on the floor is the best protection you can buy. Ideally,
it should be like a trench drainage system designed to remove fuel from
the building."
NOTE: When considering gas detection (paragraph
3.8) versus liquid sump detection, keep in mind there has to be a fume
coming off a liquid spill. There is also a continuously running ventilation
system (paragraph 3.3) changing the air over six (6) air changes an
hour, which certainly dilutes fumes in early stages of a liquid spill.
In order to have enough of a fume to be an explosive threat, there first
has to be a lot of leaked liquid chemical spread out over a large surface
area on a flat sump floor. It will take time for the spill to reach
a height of an inch or more, causing a liquid detector to alarm if there
is an optional sump sensor alarm in a drain pit. An optional
single sloped sump floor will gather (reducing its surface area) the
liquid spill along the long sump wall, and it will inch upward on the
sloped floor. It will also take time for enough evaporation to take
place to cause a gas sensor to sound an alarm. If the sloped
floor leads to a sloped trench at the end of which is an alarm drain
pit, then a very small amount of liquid would be required to reach the
end of the trench to trip an alarm. This should be the first line of
defense for protection against explosions which would be much faster
than any number of gas sensors. When a posi-ventilation system is incorporated
(as described in paragraph 3.3.2) so that the fumes are removed immediately
from over the top of the sloped trench, the explosion threat from fumes
shall be almost eliminated. This will reduce the number of gas sensors
to one or eliminate the need for them completely.
2.2.1 Optional Single Sloped Sump Floor (NFPA
30:4-4.2.6, .7, and .8) shall facilitate the natural gravity movement
of (a) air under the floor grate (cold air is heavy and falls) and heavier-than-air
fumes, gases and vapors, as well as liquid chemical spills and cleaning
water and agents to move toward the low portion of the sloped floor,
and (b) with a spill detector shall accomplish an early warning of a
liquid spill and the early warning against a liquid chemical fire or
fume explosion. The floor shall be sloped a minimum of one (1) inch
from one long wall to the other. Somewhere along the wall, at the low
edge of the sloped floor, there shall be an optional sump drain
or alarm pit (BOCA 418.3.2.6) as described in Paragraph 2.1. Installed
in the outside wall of the pit shall be an optional liquid detector
(see Paragraph 3.7). System shall pass a test at the factory whereby
gallons (it may take 2-3 gallons depending on size of sump) of water
is deliberately poured at the upper part of the sloped floor the farthest
distance from the alarm pit so that enough water shall reach and fall
into the alarm pit and trigger an alarm (less than pint). (Protected
by U.S. patent number 6, 305, 131.)
- OR -
2.2.2 Optional Double Sloped Floor shall have
sloped floors starting at each long wall and meeting at a "V"
in the center of the building or under an aisle. This shall facilitate
the movement of air, fumes and liquids, as described above in paragraph
2.2.1, and be under the optional Posi-ventilation System, as
described in paragraph 3.3.2. (Protected by U. S. patent number 6,305,131.)
- OR -
2.2.3 Optional Single or Double Sloped Sump Floor
With Sloped Trench (NFPA 30:4-4.2.7 and .8) shall facilitate the
movement of air, fumes and liquids, as described in paragraph 2.2.1
above, and provide quick and easy drainage and with an optional
drain/alarm pit and spill detector shall accomplish the speediest warning
of a liquid spill which is the earliest warning against a liquid chemical
fire or fume explosion (sloped trench not available with optional
sump liner per paragraph 2.2.3). The floor shall be sloped a minimum
of one (1) inch from (a) the long wall of the building toward the other
long wall or from (b) each long wall toward the center of the building
to a 4" wide x 1" (minimum) deep steel trench which shall
also be angled with a minimum two (2) inch drop. This option shall add
2" to the threshold height (and overall building height) for a
new threshold height of 12", assuming a 6" high sump as described
in paragraph 1.6.1, and shall require a step to be elevated to the base
of the building under the personnel doors. At the bottom end of the
trench shall be an optional alarm or drain pit as described in
Paragraph 3.6. Installed at the low end of the trench or in optional
alarm pit shall be an optional liquid spill detector (see Paragraph
3.6). System shall pass a test at the factory whereby a gallon of water
is poured at either upper part of the sloped floor at the opposite end
corner of the building from the alarm pit so that enough water shall
reach the alarm pit to raise the float (less than a pint) and trigger
an alarm. (Protected by U.S. patent number 6,305,131.)
The trench shall be located under the center of an aisle
between storage containers, etc. This shall (a) provide easiest visual
verification of a spill, (b) direct the spill out from under shelving,
work surfaces, testing devices, pumps, and containers sitting on the
elevated flooring - and prevent liquid flames from getting under these
items, and (c) expose flames from burning liquids to automatic or hand
held fire suppression materials.
2.3 Interior Fire Ratings,
Insulation, & Finishes:
(Fire ratings are based on N.F.P.A. 30, part I, 4-4.2.1,
4-4.2.2, and 4-6.4.2 fire resistant construction for flammable combustible
liquids, and the following chart is a simplification of Factory Mutual's
interpretation. Any deviations should be approved by user's Local Authority
Having Jurisdiction.) For example, the distance may increase if the
floor area exceeds 500 ft.5. Also, the AHJ must approve separation distances under
50 ft. from one hazmat building to another or from hazmat building to
user's on-site other facilities, parking lots, sidewalks, property line(s),
roads, etc., taking into account quantity, type of materials, building
construction, fire suppression systems, and explosion relief venting.)
|
HAZMAT BUILDING
DISTANCE FROM ANY WALL OR PROPERTY LINE |
HOURLY FIRE RATING
WALLS CEILING OPENINGS |
|
10' or less |
4 |
3 |
3 |
|
10' to 50' |
2 |
1 |
1-1/2 |
|
50' to 75' |
1 |
1 |
1-1/2 |
|
75' or more |
None or Noncombustible
|
2.3.1 Walls: The interior surface of the exterior
10 gauge wall plate and within the 23" wide space between each
2" x 2" vertical tubular wall member (120 lbs. blast rate)
shall be filled with 2" thick Thermax glass fiber reinforced polyisocyanurate
foam insulation board which is manufactured foamed-in-place between
sheets of aluminum foil (R-14.4). Galvanized 7/8" deep steel furring
channels shall be mechanically fastened over the Thermax onto the 2"
edge (protects against an internal fire threat) or on both sides (optional,
protects bi-directionally against external and internal fire threats)
of each 2" x 2" vertical member so that gypsum board can be
screwed to the furring, providing a thermal break between the inner
and outer wall surfaces. Optional, the 23" wide x 7/8"
deep horizontal space between channels shall be filled in with 3/4"
thick Thermax insulation board (R-5.4), bringing total insulation value
to R-19.8. The gypsum shall be 1/2" thick X-type (1 HRFR) or 3/4"
thick (2.8 lbs. ft.5) Ultracode Core (2 HRFR) or optional two (2)
layers of 3/4" thick Ultracode Core (4 HRFR) (5.6 lbs. total ft.5). (There is a 62% increase in strength from 1/2" thick gypsum panel
to 3/4" thick gypsum panel per the Hard Body Test as described
in paragraph 2.3.3.) Ultracode core panel edges shall be tapered providing
for less fastener blowouts and extra resistance to cracks caused by
thermal and hygrometric changes. Total wall thickness shall be (3-1/2",
3-3/4", or optional 4-1/2").
NOTE: When utilizing the above paragraph's optional
3/4" thick (R-5.4) horizontally applied foam board, the wall becomes
a "solid sandwich" of 10 gauge outer steel plate against a
total of 2-3/4" of foam board against 3/4" of gypsum bonded
to 22 gauge steel plate inside. The assembled wall material can add
another 39 lbs. ft.5 of blast resistance to the 120 lb. ft.5 rated building
construction as described in paragraph 1.2.2, for a total blast rating
of 159 lbs. ft.5! This stronger wall is important when upgrading from
blast resistant standards of N.F.P.A. 30 to N.F.P.A. 68 or the equivalent
Factory Mutual Property Loss Prevention Data Sheet 1-44, Damage Limiting
Construction.
Choose:
2.3.1.1 Separation
Walls: Each partition shall be either galvanized chain link or a
stainless steel trellis construction within a 2" x 2" x 1/4"
thick tubular steel wall frame that shall be wall to wall and up from
the top of the sump divider wall to the ceiling. The stainless trellis
shall be constructed of 1/8" 7 x 7 style cable in a 1' sq. design
and each "crossover" shall be held in place with stainless
steel net clips.
- OR -
2.3.1.2 Separation
Walls: Each partition shall be load bearing ( ) hour fire
rated construction, and shall meet 110 psf blast requirements from either
side. There shall be a 2" x 2" x 1/4" thick tubular steel
vertical member every 2' on center and welded to the floor/sump wall
tube and the ceiling rafter. On one side of the vertical tubes shall
be welded continuously 10 gauge plate steel for a water and air tight
seal at floor, walls, and roof (NFPA 30:4-4.2.1). On both sides of the
above wall, a ( ) thick layer of ( ) gypsum shall be screwed
to the wall. Permanently bonded to the gypsum shall be a sheet of cold
rolled steel which has been finished with a baked-on porcelain enamel.
2.3.2 Ceiling: The 23" wide space between
each 4" deep C-channel in the roof shall be filled with 2",
2-1/2", or 4" thick Thermax (R-15, R-22, or R-30) insulation
board. Galvanized 7/8" deep steel furring channels shall be mechanically
fastened over the Thermax insulation on the bottom edge of the C-channels
so that gypsum board can be screwed to the furring (also provides a
thermal break between the inner ceiling steel sheet or gypsum and outer
roof steel plate). The gypsum shall be 1/2" thick X-type (1 HRFR)
or optional 1/2" thick X-type and 3/4" Ultracode Core
(3 HRFR).
2.3.3 Ceramic Steel Interior Finish: Porcelain
enamel steel sheet shall be seen on all exterior walls (white) and ceiling
to provide a highly reflective surface for light distribution and extra
fire resistance quality through the reflection of a fire's radiant heat
rays. The steel sheets shall have been chemically coated, rinsed and
ceramic frit coated on both sides before passing through a furnace at
1,450 degrees Fahrenheit (softening the steel, thereby allowing the
ground coat to fuse or become a part of the steel). Two (2) coats of
powdered ceramic frit shall have been sprayed onto the top surface of
the steel before re-entering the furnace (each coat), creating a hardened,
extremely rugged, non-chalking, corrosion resistant, maintenance-free
porcelain enamel finished surface exceeding PEI T-21 (ASTM C-282) Class
A acid resistance standard. Combination 3/4" Thick Ultracode Core
Gypsum Bonded to 22 Gauge Sheet shall exceed 250 lbs. sq. ft. strength
test. (Wall stiffness is measured by U.S. Gypsum Hard Body Test simulating
a sledge hammer slamming into a 2' square panel.) Wear characteristics
shall be greater than 1000 cycles (per ASTM D4060 using Taber Abrason
Model 140 PT, S/N 62338, type H22 wheels) with no wear seen through
substrate. The steel clad gypsum panels shall be secured to the walls
and ceiling with exposed drywall screws every 12" in one direction
and 24" in the other, per UL Design Standards fastening pattern.
All screws holding fire rated gypsum in place shall be exposed to permit
visual inspection as well as allow for removal and replacement in order
to inspect within the wall. Screw heads, spaced across panel surface,
shall be covered with color matched snap-on plastic caps. Cracks in
seams, joints, and corners shall be filled in with fire rated caulk.
2.3.4 Custom Extruded Aluminum Trim Detail shall
be mechanically applied on all joints and corners to overlap the surfaces
of the above porcelain enamel steel finished gypsum at the butt joints,
providing protection over saw cut or curled edges. There shall be precision
molded 3" wide "flat" bar and a bi-directional corner
bar with 1-1/2" sides and a 2-1/4" high base/openings
bar, each with concave back surface(s) and a 96E angle (inside corners) on the corner bar, allowing
only the outer edge of the bars to contact the surfaces of adjoining
panels, providing a tight hairline fit once screwed into place. Optional:
Prior to fastening the trim bar, there shall be a heavy bead of silicone
(or optional fire rated) caulk applied to fill in the space between
the "flat" and corner bars and panel surfaces, eliminating
the unlikely chance of crevices where contaminants can collect or moisture
getting in due to frequent hose washdowns of the walls and ceiling.
2.3.5 Optional Floor: Under the 10 gauge plate
floor shall be 2" of Thermax insulation (R-15) which shall slide
in on top of a 14 gauge galvanized steel plate fully welded to angles
welded approximately 2-1/4" down from the 10 gauge sump floor plate.
Each 2' wide insulation panel shall be removable from under the floor
(for inspections and in case of an improbable leak and repair requires
welding). There shall be a 1/4" thick aluminum cover plate bolted
onto the building to cover the ends of the foam insulation. Floor insulation
required with A/C or cooling system equipped buildings to prevent premature
moisture condensation and rust under sump floor pan.
2.3.6 Non-Combustible Interior shall be non-fire
rated painted steel showing each 1/4" thick tubular steel member
of the building's frame as well as the back side of the 10 gauge plate
welded to the outside of the framing which is described in paragraph
1.2.
2.4 Doors:
NOTE: An open door (swing or overhead) will interfere
with the planned air flow of the mechanical ventilation system as described
in paragraphs 2.5 and 3.3. The intake air will come into
the opening in the open doorway and not through the air intake vent
opening. This will cause large dead air pockets where dangerous heavier-than-air
fumes will build up. Optional sloped trench and posi-ventilation
would eliminate this hazard. (See paragraphs 2.2 and 3.3.2.)
2.4.1 One (two, three, etc.) ( ) ( ) Wide x ( ) High
Standard Fire (Only) Door(s) and Frame(s) shall be spot welded (to
prevent deflection, warping, or jamming of the steel door in the frame)
within the wall's 2" x 4" quarter-inch thick tubular steel
jamb. (Personnel door is the only way to provide for emergency exit
with panic bar option should a worker be trapped in building equipped
with only roll-up doors that have the chain operator installed outside
the building.) Door manufacturer's frame shall be 16 gauge steel. Door
leaf shall have 16 gauge steel top, bottom, and side channels with 18
gauge steel skin front and back. Door shall be assembled and dressed
smooth with invisible seamless finish. The door and frame shall be U.L.
approved and AB@, AC@ labeled 1-1/2 or AA@ labeled 3 hour fire rated and Class A rated for 1 million open/close cycles
per ANSI A151.1. Each door shall be equipped with U.L. listed keyed
cylindrical lockset, three (3) 4.5" high x .134" thick steel
ball bearing hinges (Hinges exposed on exterior of building can be removed
allowing intruders entry. See paragraph 2.4.2 below for hingeless door
with greater security.), (optional low profile panic hardware
(on single door, or on active leaf of double door), manual top and bottom
surface bolts on inactive leaf of double door (for three point locking),
optional closer(s) with 165 degrees Fahrenheit fusible link hold
open device, (NFPA 30 para. 4.4.2.2, "...Such doors shall be permitted
to be arranged to stay open during material handling operations if the
doors are designed to close automatically..."), optional
automatic gravity operated coordinating device on double leaf doors
to assure 3/4" astragal on active leaf closes over top of "inactive"
leaf in order to seal building(s) or room(s), and optional automatic
flush bolts at the top and bottom of inactive leaf of double door. The
"hollow" door interior shall be filled with one inch cell,
99 lb. test resin impregnated honeycomb. (Optional "hollow"
interior shall have polyurethane foamed in place after door is assembled
with final expansion, curing, and chemical bonding to all interior galvanized
steel surfaces while door is compressed between platens. Insulated door
shall have an R factor of 15.)
- OR -
2.4.2 Optional One (Two, Three, etc.) ( ) ( ) Wide
x ( ) High Standard VLR (Blast) and Fire Door(s) shall be "frameless"
mounted within the wall's 1/4" thick tubular steel door jamb using
a continuous semi-concealed hinge eliminating any projecting common
hinge knuckles. The body of the door shall be 1-3/4" thick stressed
steel structure without point loading. Door(s) shall have 18 gauge steel
skins bonded to the core and welded to top, bottom and side channels
and internal 16 gauge steel horizontal stiffeners on 12" centers.
Continuous locking channel and hinge shall provide a tested 180 lbs.
ft.5 VLR blast rating. The lever shall be compatible with any standard cam
mortise cylinder. Door(s) shall be 1-1/2 (B, C labels) and 3 (A-label)
hour fire rated and cycle tested to over 1 million cycles as tested
by Warnock Hersey to be in compliance with U.L. 10C; N.F.P.A. 352; ASTME
152 and UBC standard 7-2, parts I and II. Optional low profile
panic hardware, closer(s) with 165E F fusible link door hold open device (N.F.P.A. para
4.4.2.2, "...Such doors shall be permitted to be arranged to stay
open during material handling operations if the doors are designed to
close automatically...") sides and head, gasketing (passed TAS
202 air infiltration tests with actual 0.01 CFM/ft.5 with allowable
0.50 CFM/ft.5), Pemko 185AP threshold, sweeps, glazing: wire glass
(1-1/2 hr.), ceramic (3 HR) fire rated electrically operated doors and
locking functions. The continuous locking channel and hinge shall eliminate
the need for vertical rods, top and bottom manual or automatic flush
bolts, door coordinators, astragals and floor and upper frame strikes.
The hollow core shall have an insulation value of R-4.76.
- OR -
2.4.3 Optional One (Two, Three, etc.) ( ) ( ) Wide
x ( ) High Custom Blast Door(s) and Frame(s) shall be spot welded
and mechanically fastened with a minimum of (6) 5/8" and (8) 3/8"
screws alternately spaced and driven into a 2" x 4" x 1/4"
tubular steel jamb and header. The door(s) shall be designed with minimum
14 gauge frames and skins to withstand ( ) lbs. per sq. ft. total
static loading with 100% rebound and be operatable after the blast.
(Factory Mutual Property Loss Prevention Data Sheet 1-44, Damage Limiting
Construction, paragraph 2.3, 2b states, "All doors should be capable
of resisting the same overpressures as the wall.") Door and frame
shall be U.L. approved and labeled 1-1/2 or 3 hour fire rated and Class
A rated for over 1 million open/close cycles per ANSI A151.1. All doors
shall be equipped with (3) 5" x 4-1/2" stainless steel hinges,
exterior 165 degrees Fahrenheit fusible link released hold-open/closing
device, and interior surface mounted panic hardware. Single door(s)
shall have double aught series mortise keyed lock(s). Double door(s)
shall have top and automatic latches with concealed vertical control
rods. There shall be a keyed lock and a 3/4" astragal (to seal
the space between the "active" and "inactive" leafs)
on the "active" door and an automatic coordinating device
on the header to assure the active door always closes over the inactive
door. All doors shall be R-7 insulated and weatherstripped.
2.4.4 One (Two, Three, etc.) ( ) Overhead Roll Up
Door(s), 9' or 13'4" wide x ( ) high, shall be provided
to accommodate the handling of two (2) or three (3) 48" wide pallets
being forklifted into the building with 4" to spare on each side
of the door jambs and between the pallets, and 6" above 36"
high drums on 4" high pallets to the above rack or door header.
Doors shall be installed in accordance with NFPA 80 Standard for Fire
Doors, 1995 edition. Guides shall be attached to the jambs with bolts
every 18" per FM approval procedure. Door(s) shall be three (3)
hour fire rated and manually chain operated. Automatic closure activated
by melting link shall have a speed governor controlling the door to
close at an average speed of not less than 6 inches per second and not
more than 24 inches per second. (NFPA 30 para. 4.4.2.2, "...Such
doors shall be permitted to be arranged to stay open during material
handling operations if the doors are designed to close automatically...")
Door(s) shall be mounted between 1/4" tubular jambs
(to prevent deflection, warping, or jamming of the door while building
is being shipped or being bumped into by a forklift). The door(s) shall
hang 3" out from the building wall and either (a) 3" down
from the door threshold, or (b) touch the slope of the ramp, allowing
wind blown rain that gets through joints in the curtain slats or moisture
from condensation on the door's curtain to drain out from the
building and not into the sump. The hood shall be concealed within
the building's wall structure as it extends six (6) inches out and six
(6) inches into the building with 165 degree fusible link attached to
the interior ceiling (NFPA 30: 4-4.2.2). This installation method
shall have the curl part of every slat of the door curtain face toward
the inside of the building, allowing the arched smooth surface of the
slats to face the weather side. The overhead door's mechanical components,
manual chain, optional motor, etc. shall all be inside the building,
protected from vandalism, wind blown debris, rain, snow, and
ice. (A worker trapped in the building could manually use the
chain to get out of the building should motor operation fail.) The
back of the door's hood (now facing out from the building) shall be
constructed to resist accidental forklift mast and load damage by
welding a combination 6" x 6" x 3/8" and 1" x 1"
x 1/8" steel angles at the top of the rough wall opening and a
2" x 2" x 3/16 angle at the bottom, all welded in place before
bolting on a 10 gauge steel face plate. (This application of overhead
roll up doors in a hazmat building is protected by U.S. Patent No. 5,301,479.)
Optional door(s) shall have an explosion-proof, electric, drip-proof
motor, removable without affecting auxiliary hand chain operator or
setting off limit switches. All electric components wired to a terminal
block in control panel. Up, down, and stop push-button station shall
be in NEMA 1 enclosure.
Optional Door(s) shall be installed on the exterior
surface of the 1/4" thick tubular frame rough opening with the
exposed 24 gauge steel hood and all mechanical components suspended
out (exposed to forklift hazards, weather damage and vandalism) from
the exterior wall approximately 24" and 18" above the roof.
(This conventional installation method allows for up to 20" reduced
interior ceiling height.) Should a worker become trapped inside building
and the chain operator is outside the building, there isn't a means
for exit. Optional motor operation shall be the same as above
except with non-classified electrical components.
Optional Thermal Strip Curtain shall be installed
on the inside of the overhead rollup door opening to create a trapped
air space for insulation purposes. (The strip curtain reduces the amount
of condensation on the steel slats of the door. When the overhead door
is opened or left open, the curtain shall, in the summer, prevent cold
refrigerated air from leaving the building and resist humidity from
entering, and in the winter shall prevent liquid materials [stored too
close to the uninsulated steel slats] from freezing.) The strip curtain
shall be installed up against the ceiling (not under the hood of the
door) and shall be along the length and sides of the hood. The curtain
sides shall touch the wall of the building. In addition, the curtain
shall extend to the floor of the building, which under the bottom edge
of the curtain shall be 1/4" thick painted steel plate that shall
be flushed with the rest of the elevated floor, as described in paragraph
1.6.2. This installed method shall provide a trapped pocket of air between
the curtain and the overhead door.
2.4.5 One (Two, Three, etc.) ( ) ( ) Wide x ( ) High
Cooler Door(s) and Frame(s) shall be mechanically fastened within
2" x 4" x 1/4" thick tubular steel jamb that is continuously
welded to the tubular skeleton of the building to prevent deflection,
warping, or jamming for the life of the building. The (each) door shall
have 5" foamed-in-place insulation (R-37). The door hardware shall
have three (3) heavy duty ball bearing steel hinges, one (1) three-point
compression latch with inside safety release handle, outside pull handle,
and locking capability. Optional: the door frame and sill shall
enclose a 115 V heater cable with continuously Aon@ operation without the need for thermostat control. Door and frame shall
be clad in 20 gauge G-90 galvanized coated steel inside and out. Optional
thermal strip curtain shall be installed on the inside of the cooler
door opening to create a trapped air space for insulation purposes.
(When the cooler door is opened or left open, the curtain shall prevent
cold refrigerated air from leaving the building and resist humidity
from entering.) Optional drop-down shutter shall be installed
on the inside of the door opening so that opening has 3 HR fire rating
(similar in operation to shutter description in Paragraph 2.6.3).
2.5 One (1) Low Level
Gravity or Air Intake Vent shall be provided to minimize accumulation
of heavier than air hazardous vapors. The vent shall be framed with
tubular steel and recess mounted on exterior wall at 12" above
the floor grating (N.F.P.A. 30, para. 4-4.2.11 and BOCA para. 418.3.2.8).
Unit shall be minimum of 22" square (N.F.P.A. 395, para. 2-2.7.1)
with a fixed outside louver designed to keep rain out. The vent shall
have a UL approved 1-1/2 hour or 3 hour fire rated damper with folding
blades held open by a 165 degree fusible link and a 1/4" bird screen.
In mechanical ventilation (See paragraph 3.3 to attain minimum required
6.5 air changes calculated and confirmed by testing), the vent opening
shall be at floor level with an optional 10 gauge steel duct
chase or blast hood installed over the air intake opening down to an
opening in the elevated flooring (not used with posi-vent system). This
shall cause the outside fresh air to sweep across the bottom of the
sump and reduce the need for optional pre-heating (see paragraphs 3.11
and 3.12) of cold or pre-conditioning of hot, humid air coming into
the building. Optional the vent openings shall have a 10 gauge
steel blast/rain hood (in lieu of rain louver) installed over the air
intake vent opening on the outside of the building (resists blast driven
objects from flying out of room).
2.6 Optional Explosion
Relief Vent Systems: Background - (A) There is a dichotomy between
fire and blast requirements wherein blast relief vent(s) or panel(s)
cannot be fire rated as described in N.F.P.A. 68 and FM 1-44 because
of lightweight construction constraints. Fire rated drop-down shutters
are available as in paragraph 3.6.2.2. (B) Different calculations for
total sq. ft. of open vent or panel area required are in N.F.P.A. 30
as defined by FM Class Number 6049, NFPA 68 and FM 1-44. (C) Blast relief
vent(s) or panel(s) may be substituted with mechanical ventilation as
recommended in these codes: (1) N.F.P.A. 69 Explosion Prevention Systems
1992 Edition, Chapter 3, (2) BOCA National Building Code/1999 Paragraph
418.3.1.4, "Explosion Relief: Means for explosion relief shall
be provided as specified in Sections 417.5.1, OR spaces shall be equipped with equivalent mechanical
ventilation... ", and (3) 2000 International FireCode, paragraph
911.1 which states, "...Such areas shall be provided with explosion
venting, explosion prevention systems or barricades...". Please
refer to this specification paragraph number 3.3.3 describing low level
dual fan posi-ventilation system (paragraph 3.3.1 and 3.3.2) and sloped
sump floors (paragraph 2.2) are prevention systems or a substitute for
explosion relief panels and blast shafts.
2.6.1 One (Two, Three, etc.) ( ) 8' Wide x 4' High
and One (Two, Three, etc.) 4' Square Explosion Relief Wall Panel(s)
shall be mechanically installed up close to the ceiling within a 1/4"
thick tubular steel jamb to prevent deflection, or warping during shipping
and placement of building which may cause panels to malfunction. (Roof
top panels shall not be acceptable due to potential build-up of ice,
snow, dirt and debris. In addition, the hottest temperature from an
internal fire shall be at the ceiling, causing ceiling panels to be
destroyed before wall panels. Number of panels in this spec shall exceed
1 sq. ft. of open clear opening for every 50 cu. ft. of internal building
volume (including volume within sump) as classified in Factory Mutual
Standard 6049, which is based on N.F.P.A. 30. Larger ft.5 required utilizing N.F.P.A. 68 formula or Factory Mutual
Property Loss Prevention Data Sheets 1-44.) The panel(s) shall pivot
from the bottom, utilizing a .625" diameter hinge and open 60 degrees
at the end of safety cable tethered to the top of panel frame. (Escaping
explosion gases shall exit up and outwardly - and not down.) There shall
be a shock absorbing device cushioning panel at full open and a flip-out
arm to hold open panel to allow return air in during implosion phase.
Panel shall be resettable and operable after testing, explosion or being
pulled open by high winds. The panel shall have a patented magnetic
release approved by Factory Mutual for adjustable settings from 15 -
30 lbs./sq. ft. and be preset at factory for 20 lbs.
Explosion relief panel's head, sill, jamb, and mullion
frame members shall be one-piece extruded aluminum with interior compression
gaskets to minimize air leakage and rain water entrainment when closed.
Within the frame shall be 2" foam insulation (R-9) sandwiched between
aluminum sheets. This lightweight construction shall not exceed a total
of 33 ft.5 and 2.5 lbs./ft.5 for quick release
over inertia per NFPA 68 "Standards for Venting Deflagrations."
Each panel shall be labeled with the Factory Mutual (FM) mark and, upon
request, a |