WRONG
 |
WRONG
 |
| Air
intake at lower level so heavier than air vapors are drawn up past
where workers breathe and discharge at ceiling height. Pockets of
fumes collect under fan. Cheap way to try to combine lower and upper
level ventilation systems. |
Air
intake same as graphic "A" with air mixing with heavier
than air vapors and exhausting at low level. Problem is vapors are
directed downward and condense back into a liquid chemical state
that infuses with plants and earth. |
GOOD |
BETTER |
|
|
|
| Air
intake mixing with heavier than air vapors and exhausting at low
level same as graphic "B." Gasses are directed up outside
duct chase and discharged at roof line. Even better, the fan could
be above the roof to meet N.F.P.A.91 para. 2-4.5.1 as shown in graphic
"D" on right. Dual ventilation systems have fan #1 running
continuously with sensor turning on fan #2 and sounding malfunction
alarm. |
Same
as graphic "C" plus the incoming air is forced down past
elevated floor by an inside duct where it mixes with heavier than
air vapors and is drawn out of the sump through a duct up to the
exhaust opening in the wall. Hot air at ceiling is removed by a
thermostat opening motorized dampers at vent openings located near
ceiling. System works best when energizing fan #2 for the upper
level ventilation system. |
BEST |
| The
previous Graphics "A" through "D" show ventilation
systems attempting to remove heavier-than-air vapors or fumes from
the total volume of air in the building. Explosive fumes can begin
anywhere in the building as they come off a leaked or spilled chemical
liquid. Gravity will eventually pull all heavier-than-air fumes
down into the sump floor area. When the sump floor is sloped (U.S.
Patent #6,305,131) downward toward a sloped trench (same patent),
the liquid can be collected into a smaller exposed surface area
reducing the amount of vapor coming off the liquid chemical. By
placing a posi-ventilation tube (becomes part of the elevated floor
supports) inches over the sloped trench, these fumes can be removed
from the building. Graphic "E" (y-axis) shows the posi-vent
tube (patent pending) with strategically placed holes on its bottom
surface where air and fumes are picked up and directed out of the
building wall, up a duct to a continuously running exhaust fan #1
on the roof. Graphic "F" (x-axis) shows a cross section
view of same floor of building and Click
Here to provide a close-up detail of posi-tube over the sloped
trench. If fan #1 malfunctions, a flow sensor sounds an alarm and
turns on fan #2. Both fans could be on an emergency generator or
standby circuit. A posi-ventilation dual exhaust fan system eliminates
costly non-fire rated explosion relief panels, fire rated drop down
shutters and blast shafts (U.S. Patent #6,223,473B1). |