Dual Ventilation Fan System

At rear of building, fan #1 over fan #2.

Fans #1 and #2 side-by-side on separate ducts, which lead down to inside separate low level air exhaust vents. Continuously run fan on right with emergency air flow switch to turn on second fan and sound trouble alarm. Fans mounted on outside duct. Dual fans system in combination with posi-vent system over sloped trench, eliminates need for explosion relief panels.
Dual low level ventilation draws air across the floor to exhaust vents through outside wall and up duct chase to fans on roof. Fan #1 runs continuously until malfunction alarm turns on fan #2.

Lower & Upper Level Ventilation System Comparison

GOOD BETTER
Air intake mixing with heavier than air vapors and exhausting at low level same as vent opening. Gasses are directed up outside duct chase and discharged at roof line. Even better, the fan could be above the roof to meet N.F.P.A.91 para. 2-4.5.1 as shown in graphic "D" on right. Dual ventilation systems have fan #1 running continuously with sensor turning on fan #2 and sounding malfunction alarm. Same as graphic "C" plus the incoming air is forced down past elevated floor by an inside duct or hood where it mixes with heavier than air vapors and is drawn out of the sump through a duct up to the exhaust opening in the wall. Hood (#1) shields opening from small objects turned into projectiles during explosions and (#2) keeps stored liquids from freezing in incoming cold air. Hot air at ceiling is removed by a thermostat opening motorized dampers at vent openings located near ceiling. System works best when energizing fan #2 for the upper level ventilation system.

BEST
Single Ventilation Fans
The previous Graphics "C" through "D" show ventilation systems attempting to remove heavier-than-air vapors or fumes from the total volume of air in the building. Explosive fumes can begin anywhere in the building as they come off a leaked or spilled chemical liquid. Gravity will eventually pull all heavier-than-air fumes down into the sump floor area. When the sump floor is sloped (U.S. Patent #6,305,131) downward toward a sloped trench (same patent), the liquid can be collected into a smaller exposed surface area reducing the amount of vapor coming off the liquid chemical. By placing a posi-ventilation tube (becomes part of the elevated floor supports) inches over the sloped trench, these fumes can be removed from the building. Graphic "E" (y-axis) shows the posi-vent tube (patent pending) with strategically placed holes on its bottom surface where air and fumes are picked up and directed out of the building wall, up a duct to a continuously running exhaust fan #1 on the roof. Graphic "F" (x-axis) shows a cross section view of same floor of building and Click Here to provide a close-up detail of posi-tube over the sloped trench. If fan #1 malfunctions, a flow sensor sounds an alarm and turns on fan #2. Both fans could be on an emergency generator or standby circuit. A posi-ventilation dual exhaust fan system eliminates costly non-fire rated explosion relief panels, fire rated drop down shutters and blast shafts (U.S. Patent #6,223,473B1).
www.uspto.gov c